58
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
16.4.4
For the General tab,
16.4.5
Ensure that the Byte Order and Comm Mode match the selections made in step 16.1.1.
16.4.6
Check ‘Start Polling’. Set the Starting Request to 1 and the Number of Requests to match
the total number of separate rows defined in the Master Table tab below.
16.4.7
Select the Enabled radio button in the Continuous Polling group box.