116
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
P.
Model 355 Modbus Registers
HART parameter
Modbus Register Info
Modbus Register Number
Data
Type
Number
Type
Device
Mode
HMA Mode
Slave
1
Slave
2
Slave
3
Slave
4
Slave
5
PV value
Float
2
Input
1302
1302 1312 1322 1332 1342
SV value
Float
2
Input
1304
1304 1314 1324 1334 1344
TV value
Float
2
Input
1306
1306 1316 1326 1336 1346
QV value
Float
2
Input
1308
1308 1318 1328 1338 1348
PV units code
UINT8
1
Input
104
104
124
144
164
184
SV units code
UINT8
1
Input
108
108
128
148
168
188
TV units code
UINT8
1
Input
112
112
132
152
172
192
QV units code
UINT8
1
Input
116
116
136
156
176
196
Command 48 status
bytes
UINT8
2
Input
1101-
1102
1101-
1102
1111-
1112
1121-
1122
1131-
1132
1141-
1142
Serial Number
UINT8
6
Input
2100
2100 2200 2300 2400 2500
Software version
UINT8
6
Input
2112
2112 2212 2312 2412 2512
Reserved/Unused
Blocking Distance
Float
2
Holding
3100
3100 3200 3300 3400 3500
Level Unit
code
UINT8
1
Input
2140
2140 2240 2340 2440 2540
Level Offset
Float
2
Holding
3102
3102 3202 3302 3402 3502
Level Unit code
UINT8
1
Input
2141
2141 2241 2341 2441 2541
Range
Float
2
Holding
3104
3104 3204 3304 3404 3504
Level Unit code
UINT8
1
Input
2142
2142 2242 2342 2442 2542
Damping Value
Float
2
Holding
3106
3106 3206 3306 3406 3506
Reference Distance
Float
2
Holding
3108
3108 3208 3308 3408 3508
Level Unit code
UINT8
1
Input
2144
2144 2244 2344 2444 2544
Reserved/Unused
Password
UINT16
1
Holding
3120
3120 3220 3320 3420 3520
Reserved/Unused
Device variable assigned
to
SV
UINT8
1
Holding
3130
3130 3230 3330 3430 3530
Peak Threshold
UINT8
1
Holding
3131
3131 3231 3331 3431 3531
TVG
UINT8
1
Holding
3132
3132 3232 3332 3432 3532
Reserved/Unused
Echo Strength
UINT8
1
Input
2160
2160 2260 2360 2460 2560
Содержание Jupiter JM4