214323
145
Revision B
4.6.2
Checking Voltage Range from Combine Cab
–
Case IH 5130/6130/7130;
5140/6140/7140
To ensure that the auto header height control (AHHC) system on your header works correctly with your Case IH 5, 6, and 7
(Midrange) series combine, the output voltage from the header height control sensors must be verified.
NOTE:
Changes may have been made to combine controls or display since this document was published. Refer to combine
operator
’
s manual for updates.
DANGER
Check to be sure all bystanders have cleared the area.
1.
Position the header 150 mm (6 in.) above the ground and unlock the adapter float.
1001416
A
B
Figure 4.26: Float Lock
2.
Ensure that the float lock linkage is on the down stops at
both locations. When the linkage is on the down stops,
washer (A) and nut (B) cannot be moved.
NOTE:
If the header is not on the down stops during this
procedure, the voltage may go out of range during header
operation. This will cause the AHHC system to malfunction.
1003464
A
B
Figure 4.27: Float Indicator Box
3.
Adjust cable take-up bracket (B) (if necessary) until
pointer (A) on the float indicator is on 0.
4.
Ensure that the header float is unlocked.