Instruction Manual MC6000
7-15
7.4.2
Example: Reference Value Input using Serial Interface
Torque values are to be transferred to a drive via the Serial Interface. How should the parameters
be set?
Solution:
Use the Five-Point Plan for the configuration.
The parameters in area _SIO should be checked and matched up if necessary. This may be
necessary particularly for the baud rate (SBAUD) and the device address (SADDR). The drive
will then be controlled using control word SCTL1.
Do not forget to bridge signal ENPO to + 24 V!
Parameter
Setting
Area
1. Read in SmartCard with
motor data
2. Select control mode
CFCON
TCON
_CONF
3. Select control location
CLSEL
SIO
_CONF
4. Do not set function selectors as no
_CONF
inputs or outputs are required
5. Program reference value input:
_REF
Use reference value channel 1,
RSSL1
RSIO
switch off other channels
RSSL2
RCON
RSSL3
RCON
RSSL4
RCON