363-208-010
Installation Procedures
Issue 5
May 1997
2-13
MDS Assembly Installation
NOTE
:
The maximum number of MDS assemblies which can be installed in the RT
Bay is four. The first shelf must be located at the bottom of the bay even if it
is the only shelf provided.
NOTE
:
The growth pattern for the MDS shelves is from the bottom up. Do not
leave any vacant spaces between or below the shelves. Only the first MDS
assembly will have a small space below its bay position.
J1C265AB-1 MDS Assembly Mounting Procedure
Step 1:
Open the carton and inspect the shelf and all its connectors and cable
assemblies for damage or misalignment.
Step 2:
Mount the assembly using its attached hardware to its designated bay
position. Use the alignment pins to position the assembly.
Step 3:
Locate the ground strap attached to each assembly and connect it to the
bay frame as indicated in the Figure 2-5.
NOTE
:
Remove any paint as necessary on the bay frame to ensure a
low-resistance contact.
Step 4:
Move the attached shelf cable assemblies forward so that they drape
into the bay frame’s cable duct areas. Leave the connectors in place at
this time for future connection to the Intrabay and Customer Interface
cable assemblies.
NOTE
:
The following connectors on the shelf dangler cables should be
visible in their respective ducts:
Left Duct
Right Duct
P301
J302
P101
P500
P102
P201
Содержание SLC-2000 Access System Central Office Terminal
Страница 1: ...SLC 2000 Access System Customer Assembly Manual for RT Frames 363 208 010 Issue 5 May 1997...
Страница 4: ...This page is intentionally blank...
Страница 10: ...viii Issue 5 May 1997 Contents...
Страница 16: ...xiv Issue 5 May 1997 Tables...
Страница 24: ...1 ii Issue 5 May 1997 Contents General Information...
Страница 34: ...2 iv Issue 5 May 1997 Tables Installation Procedures 2 1 Dimensions for Figure 2 2 6...
Страница 66: ...3 viii Issue 5 May 1997 Contents Cabling Wiring and Assembly...