Lucent Technologies Lineage
®
2000 ECS-6U Controller J85501E-1
Issue 4 August 1998
Acceptance Testing 5 - 9
4. Disconnect the lead from the resistor, and note that the
alarms retire and the NORM LED turns on.
5. Remove the resistor from TB101 pin 4, and connect it to
the Ringer Minor Alarm input (RMN) on pin 5 of TB101.
6. Touch the wire to the free end of the resistor. Again, the
NORM LED should extinguish and the following power
minor alarms should appear on the controller terminal
blocks or office alarm system.
PMNE, PMNA, and PMNV
7. When finished, disconnect the lead and the resistor from
both ends. Close the controller front panel.