Lucent Technologies Lineage
®
2000 ECS-6U Controller J85501E-1
Issue 4 August 1998
Installation and Setup 4 - 17
Table 4-E: Non-Lucent Technologies
Rectifier Control Signals
Signal
Designation
Signal Description
R+
Positive voltage from point of regulation
R-
Negative voltage from point of regulation
RSRSR
Restart, Restart Return: An isolated contact
closure that is sent from the controller to the
rectifier to attempt to restart the rectifier after a
HV shutdown
BAT
Battery Plant Voltage: Sent from the controller
to the rectifier (if needed) to operate alarm and
control relays
TRO
A contact closure to HVRO sent from the
controller to the rectifier to shut the rectifier
down remotely
EQO
A contact closure to HVRO sent from the
controller to the rectifier to activate the equalize
circuit in the rectifier
HVO
A contact closure to HVRO sent from the
controller to the rectifier during a high voltage
condition
HVRO
Return for all alarm leads. This lead should be
connected to ground at the rectifier
TRHO
TR Handshake. A closure to ground provided
by the rectifier after receipt of a TR signal from
the controller
RFAO
Rectifier failure alarm. A closure to rectifier
ground provided by the rectifier upon failure of
the rectifier
MANO
Manual. An open or closed contact to rectifier
ground provided by the rectifier upon being
turned off manually
ACFO
AC input failure. A closed contact to rectifier
ground provided by the rectifier upon loss of
AC input voltage