Lucent Technologies Lineage
®
2000 ECS-6U Controller J85501E-1
Issue 4 August 1998
Installation and Setup 4 - 27
Alarm Outputs: The alarm outputs (BD, HV, ACF, PMNA,
PMNV, PMNE, PMJA, PMJV, PMJE, MNF and MJF) are
isolated transfer contacts and are described functionally in
Section 2. Office alarm systems are designed for EITHER
closure-on-alarm or open-on-alarm, requiring two wires from
each controller alarm that is used.
Alarm Inputs: The alarm inputs cited above are compatible
with battery voltage on alarm signals, current-limited by
resistors. These alarm inputs are general purpose. They can be
used to detect alarm conditions from any auxiliary plant
equipment, such as ringer, converter, inverter, etc. The
subsystems generating those alarms must be powered off the
same battery and ground system as the controller (i.e., the dc
distribution bus bars). A typical application is shown
schematically in Figure 4-16. Note that the resistor value for OS
is 1000 ohms and the values for RMN and RMJ are 4640 ohms.
Control Inputs: The control inputs from an external equalize
timer panel (TEQ, TFL and TF/ER) must be connected to
Pin No.
Designation
Definition
TB104-1 PMJAC
Power Major Audible, alarm
causes closure
TB104-2
PMJAR
Power Major Audible, return
TB104-3 PMJAO
Power Major Audible, alarm
causes open
TB104-4 PMJEC
Power Major External, alarm
causes closure
TB104-5
PMJER
Power Major External, return
TB104-6 PMJEO
Power Major External, alarm
causes open
TB104-7 PMJVC
Power Major Visual, alarm
causes closure
TB104-8
PMJVR
Power Major Visual, return
TB104-9 PMJVO
Power Major Visual, alarm
causes open
TB104-10
MJFEC
Fuse Alarm Major, External,
alarm causes closure
TB104-11 MJFER
Fuse Alarm Major, External,
return
TB104-12 MJFEO
Fuse Alarm Major, External,
alarm causes open
Table 4-I: Terminal Block Pin Assignments for 113A2
Control Unit