Lucent Technologies Lineage
®
2000 ECS-6U Controller J85501E-1
4 - 24 Installation and Setup
Issue 4 August 1998
Table 4-H: AKC1B Shunt Isolator Circuit Pack
Shunt Current Programming
Shunt
Current
Rating
(Amps)
AKC1B, SW2
ECS CP1,
SW109
(see Note 1)
ECS
CP2,
SW202
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 2 3 4
50
1 1 1 1 1 1 1 0 0 1 1 0 0 0 1 1 1 0 1
75
1 0 1 0 0 0 0 0 0 1 1 0 0 0 1 1 1 0 1
100
1 0 0 0 0 0 0 0 0 1 1 0 0 0 1 1 1 0 1
150
0 1 0 0 0 0 0 0 0 1 1 0 0 0 1 1 1 0 1
200
0 0 1 0 0 0 0 0 0 1 1 0 0 0 1 1 1 0 1
250
0 0 0 1 1 1 1 1 0 1 1 0 0 0 1 1 1 0 1
300
0 0 0 1 1 1 1 0 0 1 1 0 0 0 1 1 1 0 1
400
0 0 0 0 1 1 1 0 0 1 1 0 0 0 1 1 1 0 1
500
0 0 0 0 0 0 1 0 0 1 1 0 0 0 1 1 1 0 1
600
0 0 0 0 0 0 0 0 0 1 1 0 0 0 1 1 1 0 1
800
0 0 1 0 0 0 0 0 0 1 0 1 0 0 0 0 1 1 0
1000
0 0 0 1 1 1 1 1 0 1 0 1 0 0 0 0 1 1 0
1200
0 0 0 1 1 1 1 0 0 1 0 1 0 0 0 0 1 1 0
1300
0 1 0 0 0 0 0 0 0 1 0 0 0 1 0 0 1 0 0
1500
0 0 0 0 0 0 1 1 0 1 0 1 0 0 0 0 1 1 0
2000
0 0 0 0 0 0 1 0 0 1 0 1 0 0 0 0 1 1 0
2400
0 0 0 0 0 0 0 0 0 1 0 1 0 0 0 0 1 1 0
2600
0 0 0 1 1 1 1 0 0 1 0 0 0 1 0 0 1 0 0
3000
0 0 0 0 0 1 1 0 0 1 0 0 1 0 1 1 0 1 0
4000
0 0 0 0 0 0 0 0 0 1 0 0 1 0 1 1 0 1 0
5000
0 0 0 0 0 0 1 1 0 1 0 0 1 0 0 0 0 0 0
5200
0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 1 0 0
6000
0 0 0 0 0 1 1 0 0 1 0 0 1 0 0 0 0 0 0
8000
0 0 0 0 0 0 0 0 0 1 0 0 1 0 0 0 0 0 0
10000*
0 0 0 0 0 0 1 1 0 1 0 0 0 0 0 0 1 1 1
15000*
0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 1 1
*Actual load should not exceed 8000 amperes.