Pin No.
Designation
Definition
TB101-11
TR3
Transfer Shutdown from
Engine
TB101-12
TR4
Transfer Shutdown from
Engine
TB102-1
BDEC
Battery on Discharge External,
alarm causes closure
TB102-2 BDER
Battery on Discharge External,
return
TB102-3 BDEO
Battery on Discharge External,
alarm causes open
TB102-4 HVEC
High Voltage External, alarm
causes closure
TB102-5
HVER
High Voltage External, return
TB102-6
HVEO
High Voltage External, alarm
causes open
TB102-7 ACFEC
AC Fail External, alarm causes
closure
TB102-8
ACFER
AC Fail External, return
TB102-9 ACFEO
AC Fail External, alarm causes
open
TB103-1 PMNAC
Power Minor Audible, alarm
causes closure
TB103-2
PMNAR
Power Minor Audible, return
TB103-3 PMNAO
Power Minor Audible, alarm
causes open
TB103-4 PMNEC
Power Minor External, alarm
causes closure
TB103-5
PMNER
Power Minor External, return
TB103-6 PMNEO
Power Minor External, alarm
causes open
TB103-7 MNFEC
Fuse Alarm Minor, External,
alarm causes closure
TB103-8 MNFER
Fuse Alarm Minor, External,
return
TB103-9 MNFEO
Fuse Alarm Minor, External,
alarm causes open
TB103-10
PMNVC
Power Minor Visual, alarm
causes closure
TB103-11
PMNVR
Power Minor Visual, return
TB103-12
PMNVO
Power Minor Visual, alarm
causes open
Table 4-I: Terminal Block Pin Assignments for 113A2
Control Unit