Lucent Technologies Lineage
®
2000 ECS-6U Controller J85501E-1
4 - 6 Installation and Setup
Issue 4 August 1998
terminated with a connector. The proper connectors are shipped
with each unit. Table 4-B describes the wires and their functions.
Equalize
Enable/Disable
The equalize jumper, P106 on the 113A2, is factory set in the
DISABLE position (pins 1 and 2). If the plant is equipped with
equalize-type rectifiers and flooded-type batteries, this jumper
may be moved to the ENABLE position (pins 2 and 3). When
equalize is enabled, the front panel switch and other equalize
control methods can be used to initiate equalize charging. If the
jumper is removed or misplaced, equalize is DISABLED.
CAUTION
Use of Equalize is not recommended for sealed cells.
Not all Lucent Technologies rectifiers are equipped with the
equalize feature. Use equalize only if all the rectifiers have the
equalize feature. The following is a list of Lucent Technologies
rectifiers that have the equalize feature:
Table 4-B: Wire Descriptions and Functions
Wire Color
Name
Connecting
Point to
FAB
Function
Blue
DG
P506-1
“Discharge ground” from
plant bus
Brown
RG
P506-2
“Reg ground” from plant bus
Yellow
DB
P504-1
“Discharge battery” from
plant bus
Brown
RB
P504-2
“Reg battery” from plant bus
Orange
RB
P504-3
“Reg battery” from plant bus
Orange/black
BS-
P506-3
Plant shunt connection
(negative)
Orange
BS+
P506-4
Plant shunt connection
(positive)
White/orange
CBA
E501
Connection for major fuse
alarm
White/brown
MJF
E502
Connection for major fuse
alarm
White/blue
MNF
E503
Connection for minor fuse
alarm