Chapter 2 - Operation
37
2.5.3
Operation via Keypad
1.
Check the LCD display when Power ON. Otherwise, change the setting indicated above.
2.
Set the Ref. Freq to 60 Hz using
PROG/ENT/SHIFT
,
▲
keys. Setting freq is displayed during stop.
3.
When pressing
FWD/REV
key, motor starts running and output freq and output current are displayed.
4.
Press
STOP/RESET
key. Then motor decelerates to stop. Setting freq 60Hz is displayed.
DRV▶K/K 0.0 A
00 STP 0.00Hz
Setting:
DRV-03
[Drive Mode (Run/Stop method)] =
0 (Keypad)
DRV-04
[Frequency Mode (Freq. setting method)] =
0 (Keypad-1)
DRV▶K/K 0.0 A
00 STP 60.00Hz
DRV▶K/K 5.0 A
00 FWD 60.00Hz
DRV▶K/K 0.0 A
00 STP 60.00Hz