Chapter 6 - Parameter Description [FU2]
102
[Power ON Start: ‘No’]
[Power ON Start: ‘Yes’]
☞
Note:
In case of using ‘Power ON Start’ to ‘Yes’, make
sure to utilize appropriate warning notices to minimize the
potential for injury or equipment damage.
FU2-21: Restart After Fault Reset
If FU2-21 is set to ‘Yes’, inverter will restart after the
RST (reset) terminal has been reset a fault.
If FU2-21 is set to ‘No’, restart the inverter by cycling the
FX or RX terminal to CM terminal after the fault has
been reset. If the motor is rotating by inertia at the time
power is restored, the inverter may trip. To avoid this trip,
use ‘Speed Search’ function by setting FU2-22 to ‘xx1x’.
[Reset restart: ‘No’]
[Reset restart: ‘Yes’]
☞
Note:
In case of using ‘Reset Restart’ to ‘Yes’, make sure
to utilize appropriate warning notices to minimize the
potential for injury or equipment damage.
FU2-22: Speed Search Selection (Bit Set)
FU2-23: Current Limit Level During Speed
Search
FU2-24: P Gain During Speed Search
FU2-25: I Gain During Speed Search
Input Power
Time
FX-CM
ON
Time
ON
No Effect
Start
Power On
Output Frequency
Time
Input Power
Time
FX-CM
ON
Time
Start
Power On
Output Frequency
Time
FU2► RST restart
21 --- No ---
0
21
Factory Default:
No
0
Output Frequency
Time
FX-CM
ON
Time
RST-CM
ON
Time
ON
No Effect
Start
Tripped
Output Frequency
Time
FX-CM
ON
Time
RST-CM
ON
Time
Start
Tripped
Related Functions:
FU2-22 ~ FU2-25 [Speed Search]
Related Functions:
FU2-22 ~ FU2-25 [Speed Search]
FU2►Speed Search
22 0000
0000
22
Factory Default:
0000
0000
FU2► SS Sup-Curr
23 150 %
150
23
Factory Default:
150 %
150
Содержание SV008iS5-2
Страница 28: ...Chapter 1 Installation 22 Notes ...
Страница 84: ...Chapter 5 Parameter List 78 Notes ...
Страница 92: ...Chapter 6 Parameter Description DRV 86 Notes ...
Страница 180: ...Chapter 7 Options 174 Type 2 Max 600 Watt Type 3 A ...