Chapter 6 - Parameter Description [EXT]
140
EXT-22 ~ EXT-23: Gains for ‘Sub-B’ Board
This is the proportional gain when the EXT-14 is set to
‘Feed-back’.
This is the integral gain when the EXT-14 is set to ‘Feed-
back’.
EXT-24: Slip Frequency for ‘Sub-B’ Board
This is the limit frequency the inverter uses to
compensate the motor speed drop due to load
fluctuation. The set point value is the percentage of
FUN-32 [Rated Motor Slip].
EXT-25: Sensored Vector_SPD P
This is the proportional gain when the control mode is
set to ‘Sensored Vector_SPD’.
Adjust the gain when the speed and torque response is
slow.
EXT-26: Sensored Vector_SPD I
This is the integral gain when the control mode is set to
‘Sensored Vector_SPD’.
Adjust the gain when the speed and torque response is
slow.
EXT-27: + Torque Limit
This is the Forward Torque Limit when the control mode
is set to ‘Sensored Vector_SPD’.
EXT-28: - Torque Limit
This is the Reverse Torque Limit when the control mode
is set to ‘Sensored Vector_SPD’.
EXT-30 ~ EXT-32: Multi-Function Output
Terminal (Q1, Q2, Q3) Define – Sub-A, Sub-C
Q1, Q2, Q3 terminals are provided on Sub-A and Sub-C
board as an open collector output. The functions of
these terminals can be selected the same as I/O-44
[Multi-function Auxiliary Contact Output Define].
EXT► PG P-gain
22 3000
3000
22
Factory Default:
3000
3000
EXT► PG I-gain
23 50
50
23
Factory Default:
50
50
EXT►PG Slip Freq
24 100 %
100
24
Factory Default:
100 %
100
EXT► Q1 define
30 FDT-1
0
30
Factory Default:
FDT-1
0
EXT► Q2 define
31 FDT-2
1
31
Factory Default:
FDT-2
1
Factory Default:
FDT-3
2
Related Functions:
FU1-54 [Overload Warning Level]
FU1-55 [Overload Warning Time]
FU1-59 [Stall Prevention Mode]
FU1-60 [Stall Prevention Level]
I/O-12 ~ I/O-14 [Multi-function Input
Terminal define]
I/O-42 ~ I/O-43 [Frequency Detection]
I/O-44 [Multi-function Auxiliary Contact
Output define]
I/O-50 ~ I/O-56 [Auto Operation]
25
Factory Default:
100 %
100
100
EXT►
ASR P-Gain
25 100 %
26
Factory Default:
200ms
200
200
EXT►
ASR I-Gain
26 200ms
27
Factory Default:
180 %
180
180
EXT►
Trq + Limit
27 180 %
28
Factory Default:
180 %
180
180
EXT►
Trq - Limit
28 180 %