Chapter 2 - Operation
25
2.2.1
LCD Keypad Display
DRV
▶
T/K 0.0 A
00 STP 0.00 Hz
Displays
Description
1) Parameter Group
Displays the parameter group. There are DRV, FU1, FU2, I/O, EXT, COM, APP groups.
2) Run/Stop Source
Displays the source of motor Run and Stop
K
: Run/Stop using FWD, REV buttons on keypad
T
: Run/Stop using control terminal input FX, RX
O
: Run/Stop via option board
3) Frequency Setting
Source
Displays the source of command frequency setting
K
: Frequency setting using keypad
V
: Frequency setting using V1 (0 ~10V) or V1 + I terminal
I:
Frequency setting using I (4 ~ 20mA) terminal
U
: Up terminal input when Up/Down operation is selected
D
: Down terminal input when Up/Down operation is selected
S
: Stop status when Up/Down operation is selected
O
: Frequency setting via Option board
X
: Frequency setting via Sub board
J
: Jog terminal input
1 ~ 8
: Step frequency operation
* During Auto operation, 2) and 3) display the ‘sequence number/step’.
4) Output Current
Displays the Output Current during operation.
5) Parameter Code
Displays the code of a group. Use the ▲(Up), ▼(Down) key to move through 0~99 codes.
6) Operating Status
Displays the operation information.
STP
: Stop Status
FWD
: During Forward operation
REV
: During Reverse operation
DCB
: During DC Braking
LOP
: Loss of Reference from Option Board (DPRAM fault)
LOR
: Loss of Reference from Option Board (Communication network fault)
LOV
: Loss of Analog Frequency Reference (V1: 0~10V)
LOI
: Loss of Analog Frequency Reference (I: 4~20mA)
LOS
: Loss of Reference from Sub-Board
7) Drive Output Frequency
Command Frequency
Displays the Output Frequency during run.
Displays the Command Frequency during stop.
2) Run/Stop Source
3) Frequency Setting Source
4) Output Current
7) Drive Output Frequency During Run,
Command Frequency During Stop
6) Operating Status
5) Parameter Code
1) Parameter group