Chapter 6. Function Description (CON)
(Example)
Programming P4 as ASR PI Gain
Code
LCD display
Description
Setting range
Unit
Set value
I/O_04
P4 define
Multi-function input terminal
P4 definition
ASR Gain Sel
The two sets of Lowpass Filter are as follow:
Code
LCD display
Description
Setting range
Unit
Factory setting
CON_05
ASR LPF1
ASR LPF time constant 1
0 ~ 20000
ms
0
CON_08
ASR LPF2
ASR LPF time constant 2
0 ~ 20000
ms
0
3)
CON_03 ~ 04(ASR PI Gain 1)
4) CON_06 ~ 07(ASR PI Gain 2)
One of 2 sets of PI gain can be selected by “ASR Gain Sel” in Multi-function input terminal.
Code
LCD display
Description
Setting range
Unit
Factory setting
CON_03
ASR P Gain1
ASR P Gain 1
0.0 ~ 200.0
%
50.0
CON_04
ASR I Gain1
ASR I Gain 1
0 ~ 50000
ms
300
CON_06
ASR P Gain2
ASR P Gain 2
0.0 ~ 200.0
%
5.0
CON_07
ASR I Gain2
ASR I Gain 2
0 ~ 50000
ms
3000
5) CON_09 (Ramp time for ASR gain Transfer)
6) CON_10 (Motor Speed at the time of ASR Gain Transfer)
ASR PI controller can be transferred to P controller depending on the status of the multi-function terminal input set
as ’
ASR P/PI transfer
’.
(Example) When P6 is set to ASR P/PI transfer:
Code
LCD display
Description
Setting range
Unit
Factory setting
I/O_06
P6 define
Multi-function input
terminal P6 definition
ASR P/PI Sel
To avoid the shock to the control system due to the rapid change P and I gain in case of ASR gain transfer, if the
multi-function terminal input set to ‘
ASR Gain Sel
’ is ‘On’, the transferred P gain changes gradually for the time set at
CON_09. P gain 2 is transferred to P gain 1 at the higher speed than the value set at CON_10. This happens when the
multi-function terminal input set to ‘ASR Gain Sel’ is ‘On’, not ‘Off”