Chapter 6. Function Description (I/O)
Code
Parameter name
LCD display
Unit
Description
Negative Trq Limit
Neg Trq Limit
%
Negative torque limit to rated torque
Regeneration Trq Limit
Reg Trq Limit
%
Regeneration torque limit to rated torque
Torque Reference
Torque Ref
%
Torque reference to rated torque
Torque current ref.
IqeRef
%
Torque current reference to rated torque current
Torque current
Iqe
%
Actual torque current to rated torque current
Flux reference
Flux Ref
%
Flux reference to the rated flux
Flux Current ref.
IdeRef
%
Flux current reference to rated flux current
Flux Current
Ide
%
Actual flux current to rated flux current
ACR output of axis Q
ACR_Q Out
V
ACR output value of axis Q
ACR output of axis D
ACR_D Out
V
ACR output value of axis D
Voltage reference of
axis D
VdeRef
V
Voltage reference value of axis D
Voltage reference of
axis Q
VqeRef
V
Voltage reference value of Q axis Q
Output current
Out Amps RMS
A
Inverter output current (rms)
Output voltage
Out Volt RMS
V
Inverter output voltage (rms)
Output power
Power
kW
Motor output power
DC LINK voltage
DC Bus Volt
V
Inverter DC link voltage
Process PI reference
Proc PI Ref
%
Reference value of Process PID routine
Process PI Feedback
Proc PI F/B
%
Feedback value of Process PID routine
Process PI output
Proc PI Out
%
Output value of Process PID routine
Motor temperature
Mot Temp
deg
Motor temp displayed. 25
℃
displayed when motor
NTC is not provided with the motor.
Inverter temperature
Inv Temp
deg Inverter Heatsink temp displayed
Inverter i2t
Inv i
2
t
%
Inverter overload capability displayed. In the case
Overload capability is 150% for 1 min, i
2
t becomes
100% when 150% of rated current is flowing for 1
min.
MOP output
MP Output
%
Set value displayed when operation is done by
potentiometer on terminal input.
Control mode
Ctrl Mode
Selected control mode displayed
Software version
S/W Version
S/W version displayed
Running time
Run Time
Inverter running time displayed after Power On
ON/OFF status of Input terminal displayed
(0: OFF, 1: ON)
FX
RX
BX
P1
P2
P3
P4
P5
P6
P7
Input terminal status
Terminal In
0 :
OFF
1 :
ON
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
ON/OFF status of open collector output, fault relay
and contact output.
(0: OFF, 1: ON)
AX1
AX2
OC1
NC
NC
30A
(30B)
Output terminal status
Terminal Out
0 : OFF
1 : ON
0/1
0/1
0/1
0
0
0/1
Running status
Run Status
Operating status displayed