Chapter 5. Function Code Table
5-5
Setting data
Functio
n code
Function name
LCD display
Range
Unit
Default
Adjustm
ent
during
run
Page
I/O_41
Definition of multi-
function
Auxiliary output (AX1)
Not Used
INV Ready
Zero Spd Det
Spd Det.
Spd Det(ABS)
Spd Arrival
Timer Out
LV Warn
Run
Regenerating
Mot OH Warn
Inv OH Warn
Spd Agree
Trq Det.
Trq Lmt Det.
OverLoad
Stop
Steady
6-21~26
I/O_42
Definition of multi-
function
Auxiliary output (AX2)
AX2 Define
Same as I/O_41
Not Used
Yes
6-21~26
I/O_43
Definition of multi-
function
Auxiliary output (OC1)
OC1 Define
Same as I/O_41
Not Used
Yes
6-21~26
I/O_46
Fault
relay
mode
selection
(A, B, C)
Relay Mode
000 ~ 111
bit
011
Yes
6-26~27
I/O_47 Zero speed detection
level
ZSD Level
0.0 ~ 480.0
rpm
10.0
Yes
6-22
I/O_48 Zero speed detection
band
ZSD Band
0.1 ~ 10.0
%
0.5
Yes
6-22
I/O_49 Speed detection level
SD Level
-3600 ~ 3600
rpm
0
Yes
6-22
I/O_50 Speed detection band
SD Band
0.1 ~ 10.0
%
0.5
Yes
6-22~23
I/O_51 Speed arrival band
SA Band
0.1 ~ 10.0
%
0.5
Yes
6-23
I/O_52 Speed deviation band
SEQ Band
0.1 ~ 10.0
%
0.5
Yes
6-23
I/O_53 Torque detection level
TD Level
0.0 ~ 250.0
%
0.0
Yes
6-25
I/O_54 Torque detection band
TD Band
0.1 ~ 10.0
%
0.5
Yes
6-25
I/O_55 Timer On delay time
TimerOn Dly
0.1 ~ 3600.0
sec
0.1
Yes
6-24
I/O_56 Timer Off delay time
TimerOff Dly
0.1 ~ 3600.0
sec
0.1
Yes
6-24
I/O_57 Overload warning level
OL Level
30 ~ 250
%
150
Yes
6-25
I/O_58 Overload warning time
OL Time
0 ~ 30
sec
10
Yes
6-26
I/O_59 Overload trip selection
OLT Select
Yes/No
Yes
Yes
6-27
I/O_60 Overload trip level
OLT Level
30 ~ 250
%
180
Yes
6-27
I/O_61 Overload trip time
OLT Time
0 ~ 60
sec
60
Yes
6-27
I/O_62 Inverter
overheat
warning temp.
IH Warn Temp
50 ~ 85
deg
75
Yes
6-25
I/O_63 Inverter
overheat
warning band
IH Warn Band
0 ~ 10
deg
5
Yes
6-25
I/O_64 Motor
overheat
warning temp.
MH
Warn
Temp
75 ~ 130
deg
120
Yes
6-25
I/O_65 Motor
overheat
warning band
MH Warn Band
0 ~ 10
deg
5
Yes
6-25