Chapter 6. Function Description (I/O)
6.2 I/O group (I/O_[][])
6.2.1 Jump code (I/O_00)
In I/O_00, jumping directly to any parameter code can be accomplished by entering the desired code number.
(Example) Moving to I/O_05
Press [PROG] and set to 5 using [SHIFT/ESC] / [
▲
(Up)] / [
▼
(Down)] and press [ENT] key to move to I/O_05. If the
desired code cannot be set, the closest code will be displayed.
Jumping other code is available using [
▲
(Up)] / [
▼
(Down)] keys.
6.2.2 Multi-function Input Terminal
1) I/O_01 ~ I/O_07 (Multi-function input terminal P1 ~ P7 define)
It defines Multi-function input terminals. SV-iV5 has 7 dedicated terminals (P1 ~ P7) for the setting of parameters
below. However, the multiple terminals cannot be selected for the same function and if so, the invalid terminal definition
is displayed as “Not Used”. And the selected function cannot be adjusted while running.
No
Set value
Description
No
Set value
Description
1
Speed-L
Multi-step speed-Low
15
Ext Trip-B
External trip B contact
2
Speed-M
Multi-step speed-Middle
16
Prohibit FWD
Forward Run Disabled
3
Speed-H
Multi-step speed-High
17
Prohibit REV
Reverse Run Disabled
4
Jog Speed
Jog speed
18
Proc PID Dis
PID operation disabled
5
MOP Up
MOP UP operation
19
Timer Input
Timer ON
6
MOP Down
MOP Down operation
20
SoftStrtCncl
Cancel Soft start
7
MOP Clear
MOP Speed Clear (Reset)
21
ASR Gain Sel
Switch ASR gain
8
MOP Save
MOP Speed Save
22
ASR P/PI Sel
Switch ASR P/PI
9
Analog Hold
Analog speed ref. Hold
23
Flux Ref Sel
Switch Flux reference
10
Main Drive
Exchange between Option and
Inverter
24
PreExcite
Pre-excitation
11
2nd Func
The 2
nd
function
25
Spd/Trq Sel
Speed/Torque control select
12
Xcel-L
Multi-accel/decel-Low
26
Use Max Trq
Torque limit ON/OFF
13
Xcel-H
Multi-accel/decel-High
27
Use Trq Bias
Torque bias ON/OFF
14
3-Wire
3 Wire
I/O
▶
P5 define
05 Not Used