Quick Start Reference
Q
viii
Verify Motor Direction
This step explains how to check motor direction by running the motor at a low speed via the
keypad in
HAND
mode. Verify that the power and motor wiring matches the previous step and
covers are installed before applying power.
At first power up, the display will look like below. “0.0 Hz” represents the default HAND frequency
reference.
Checking Direction
Use the above mentioned steps to run the motor in the forward direction in HAND mode. The
display will briefly show the output frequency of the VFD until it reaches 10Hz.
Look at the motor shaft to verify rotation is correct. Press the OFF key to STOP.
If motor direction is incorrect, stop the motor with the OFF key, and power down the VFD.
Wait at least 5 minutes to let the VFD capacitors discharge.
Swap any two output leads between the VFD and the motor. This will change motor direction.
Verify correct rotation via the previous steps.
Changing Acceleration Time - Example
1. Press the [MODE] key from the main display to access PAR Mode.
2. In the DRV group, press down to select DRV 03 (Acc Time).
3. Press the [PROG/ENT] key access the current setting.
4. Use the UP and DOWN arrows to increase and decrease the value.
5. Use the LEFT or RIGHT arrows to move the cursor over to select different digits.
6. Press the [PROG/ENT] key once the desired value is set. This saves the change.
7. DRV 03 will be displayed again indicating the parameter change has taken effect with the new
value displayed.
Press LEFT arrow 3
times so that the cursor is
flashing to the left of
“0.00”.
Press UP arrow so that 10.00
is displayed.
Press the Hand key to run the
motor in the forward direction.
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...