45
Installing
the Inverter
Note
The terminal on the right is used to ENABLE the EMC filter (factory default). The terminal on the
left is used to DISABLE the EMC filter (for power sources with asymmetrical grounding).
Disabling the Built-in EMC Filter for 110
–500 kW (3–Phase) Inverters
Follow the instructions listed below to disable the EMC filters for the H100+ inverters rated
for 110
–500 kW.
1
Remove the front cover located at the top of the inverter.
2
Remove the EMC ground cable from the right terminal (EMC filter-ON / factory
default), and connect it to the left terminal (EMC filter-OFF / for power sources with
asymmetrical grounding).
110
–132 kW (3-Phase) 160–185 kW (3-Phase)
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...