Technical Specification
187
Product (kW)
Circuit Breaker
Leakage Breaker
Magnetic Contactor
UL unapplied
UL applied
UL unapplied
note1)
UL applied
note2)
Model
Rated
Current
Model
Rated
Current
Model
Rated
Current
Model
Rated
Current
15
ABS63c
60
50
50
50
18.5
ABS103c
100
70
EBS103c
100
MC-85a
85
22
ABS103c
100
80
100
85
30
ABS103c
100
100
100
MC-100a
100
37
ABS203c
175
UTS250
150
EBS203c
200
MC-150a
150
45
ABS203c
175
150
200
150
55
ABS203c
175
150
200
150
75
ABS203c
225
225
EBS203c
225
MC-225a
225
90
ABS203c
250
250
250
MC-265a
265
110
ABS603c
500
UTS600
500
EBS603c
500
MC-400a
400
132
ABS603c
600
600
EBS603c
630
MC-400a
400
160
ABS603c
630
600
EBS603c
630
MC-630a
630
185
ABS803c
800
UTS800
800
EBS803c
800
MC-630a
630
220
ABS803c
800
800
EBS803c
800
MC-800a
800
250
ABS1003b
1000
800
EBS1003b
1000
MC-800a
800
315
ABS1203b
1200
UTS1200
1200
EBS1203b
1200
MC-1260a
1260
355
ABS1203b
1200
1200
EBS1203b
1200
MC-1260a
1260
400
-
1600
-
1600
500
-
1600
-
1600
* In the case of inverter 400/500 kW, there is no Circuit Brake capacity qualified as UL standard.
* Refer to local and national codes for proper circuit breaker sizing.
* If you want to use UL Type products, please use that ACB product.
* Note1) LS Leakage Breaker does not have a separate UL certified product.
* Note2) When using a magnetic contactor non-UL product, please use LS Susol Type(MC-
9(9A) ~ MC-95(95A).
Maximum allowed prospective short-circuit current at the input power connection is defined
in IEC 60439-1 as 100 kA. LSLV-H100+ is suitable for use in a circuit capable of delivering
not more than 100kA RMS at the drive’s maximum rated voltage, depending on the
selected MCCB. RMS symmetrical amperes for recommended MCCB are the following
table.
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...