35
Installing
the Inverter
Note
•
Apply a DC input to the P2 (+) and N (-) terminals to operate the inverter on DC voltage
input.
•
Use STP (Shielded Twisted Pair) cables to connect a remotely located motor with the
inverter. Do not use 3 core cables.
•
Make sure that the total cable length does not exceed 492 ft (150 m). For inverters < = 3.7
kW capacity, ensure that the total cable length does not exceed 165 ft (50 m).
•
Long cable runs can cause reduced motor torque in low frequency applications due to
voltage
drop. Long cable runs also increase a circuit’s susceptibility to stray capacitance
and may trigger over-current protection devices or result in malfunction of equipment
connected to the inverter.
•
Voltage drop is calculated by using the following formula:
•
Voltage Drop (V) = [√3 X cable resistance (mΩ/m) X cable length (m) X current (A)] / 1000
•
Use cables with the largest possible cross-sectional area to ensure that voltage drop is
minimized over long cable runs. Lowering the carrier frequency and installing a micro
surge filter may also help to reduce voltage drop.
Distance
< 165 ft (50 m)
< 330 ft (100 m)
> 330 ft (100 m)
Allowed Carrier Frequency
<15 kHz
<5 kHz
<2.5 kHz
Do not connect power to the inverter until installation has been fully completed and the inverter
is ready to be operated. Doing so may result in electric shock.
•
Power supply cables must be connected to the R, S, and T terminals. Connecting power
cables to other terminals will damage the inverter.
•
Use insulated ring lugs when connecting cables to R/S/T and U/V/W terminals.
•
The inverter’s power terminal connections can cause harmonics that may interfere with
other communication devices located near to the inverter. To reduce interference the
installation of noise filters or line filters may be required.
•
To avoid circuit interruption or damaging connected equipment, do not install phase-
advanced condensers, surge protection, or electronic noise filters on the output side of the
inverter.
•
Connect the MC to the output of the inverter and avoid MC ON / OFF state during
operation.
(It may cause inverter trip and burn-out.)
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...