xvii
Quick Start Reference
4. Wakeup level
▶
PID-57 WakeUpLev type
0. Absolute or 1. Deviation (Factory default) can be selected for the Wake-up level
Fe
ed
ba
ck
Wakeup
Delay time
Deviation
Absolute
Wakeup Level
=Setpoint-wakeup level
Setpoint
▶
PID-64 PID WakeUp 0 DT
▶
PID-65 PID WakeUp 0Lev
Sets the reference for PID operation in PID sleep mode. PID operation resumes when PID
feedback variation (from the PID reference) exceeds the values set in PID-65 for more than the
time set in PID-64.
5. Lost Feedback Detection Mode
Lost Feedback Detection shuts down the pump system when the feedback device failed.
The set values in [PRT-14] and [PRT-15] of frequency command parameters are also used for the
operation of Lost Feedback Detection Time and Lost Feedback Preset Frequency
▶
AP2-75 LostFbkMode
Setting
0
None
1
Warning
2
Trip & Coast
3
Lost Preset
▶
PRT-14 Lost Cmd Time
▶
PRT-15 Lost Preset Frequency
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...