Installing the Inverter
42
Step 6 Disabling the EMC Filter for Power Sources with Asymmetrical
Grounding
H100+, 400 V 0.75
–55 kW, 110~500kW(3 phase) inverters have EMC filters built-in and
activated as a factory default design. An EMC filter prevents electromagnetic interference
by reducing radio emissions from the inverter. EMC filter use is not always recommended,
as it increases leakage current. If an inverter uses a power source with an asymmetrical
grounding connection, the EMC filter must be turned off.
Asymmetrical Grounding Connection
One phase of
a delta
connection is
grounded
(TN Systems)
Intermediate
grounding
point on one
phase of a
delta
connection
(TN
Systems)
The end of a
single phase
is grounded
(TN Systems)
A 3-phase
connection
without
grounding
(TN
Systems)
•
Do not activate the EMC filter if the inverter uses a power source with an asymmetrical
grounding structure (corner-earthed systems), for example a grounded delta connection.
Personal injury or death by electric shock may result.
•
Wait at least 10 minutes before opening the covers and exposing the terminal connections.
Before starting work on the inverter, test the connections to ensure all DC voltage has been
fully discharged. Personal injury or death by electric shock may result.
Before using the inverter, confirm the power supply’s grounding system. Disable the EMC
filter if the power source has an asymmetrical grounding connection.
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...