Safety Information
•
Do not allow foreign objects, such as screws, metal chips, debris, water, or oil to get inside
the inverter. Allowing foreign objects inside the inverter may cause the inverter to
malfunction or result in a fire.
•
Do not operate the inverter with wet hands. Doing so may result in electric shock.
•
Do not modify the interior workings of the inverter. Doing so will void the warranty.
•
The inverter is designed for 3-phase motor operation. Do not use the inverter to operate a
single phase motor.
•
Do not place heavy objects on top of electric cables. Doing so may damage the cable and
result in an electric shock.
Note
Maximum allowed prospective short-circuit current at the input power connection is defined
in IEC 60439-1 as 100 kA. LSLV-H100 is suitable for use in a circuit capable of delivering
not more than 100kA RMS at the drive’s maximum rated voltage, depending on the
selected MCCB. RMS symmetrical amperes for recommended MCCB are the following
table.
Remarque
Le courant maximum de court-
circuit présumé autorisé au connecteur d’alimentation
électrique est défini dans la norme IEC 60439-1 comme égal à 100 kA. Selon le MCCB
sélectionné, la série LSLV-H100 peut être utilisée sur des circuits pouvant fournir un
courant RMS symétrique de 100 kA maximum en ampères à la tension nominale
maximale du variateur. Le tableau suivant indique le MCCB recommandé selon le courant
RMS symétrique en ampères.
Working
Voltage
UTE100
(E/N)
UTS150
(N/H/L)
UTS250
(N/H/L)
UTS400
(N/H/L)
240V(50/60Hz) 50/65kA 65/100/150kA 65/100/150kA 65/100/150kA
480V(50/60Hz) 25/35kA 35/65/100kA 35/65/100kA
35/65/100kA
Working
Voltage
ABS33c
ABS53c
ABS63c
ABS103c
ABS203c
ABS403c
240V(50/60Hz)
30kA
35kA
35kA
85kA
85kA
75kA
480V(50/60Hz)
7.5kA
10kA
10kA
26kA
26kA
35kA
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...