SFA-5000 • SFA-10000 CANopen®
To change the baud rate value you have to:
object;
send a
Reset node
command (or
Reset communication
command);
save the parameter;
set the Master to the new baud rate.
Default = 05h
Master
Encoder
COB-ID
Cmd
Index
Sub
Data byte
600+ID
2F
00
30
00
see table
Encoder
Master (confirmation)
COB-ID
Cmd
Index
Sub
Data byte
580+ID
60
00
30
00
00
Master
Encoder (
Reset node
)
COB-ID
Cmd
Slave ID
000
81
ID
Set the Master device to the new baud rate:
Encoder
Master (Boot-up with new baud rate setting)
COB-ID
Cmd
700+ID
00
NOTE
To save the new Baud rate value execute the store parameters function (see the
object).
When the power is turned off, the parameters not saved are lost.
3001-00 Node-ID
[Unsigned8, rw]
This object defines the node identifier (node ID) of the device. The node
addresses are allowed in the range 1 to 127. The default value is 1.
The node number is set through the
the DIP B dip switch are set to ”OFF”. If one bit at least of the DIP B dip switch is
set to “ON” the node number is set by DIP B. For any further information refer to
the “4.7 Setting the node address: DIP B” section on page 32.
To change the Node-ID value you have to:
object;
send a
Reset node
command;
save the parameter.
MAN SFA_5000_10000_CB E 1.0.odt
6 - CANopen® interface
57 of 88