To set the preset value you must send the following command:
Set the Preset value
(preset = 1000 = 03E8h)
Master
Encoder (Set request)
COB-ID
Cmd
Index
Sub
Process data
600+ID
23
03
60
00
E8
03
00
00
Encoder
Master (Set confirmation)
COB-ID
Cmd
Index
Sub
Process data
580+ID
60
03
60
00
00
00
00
00
NOTE
If the scaling function is disabled (see the bit 2
be less than or equal to the
Total hardware resolution
- 1 (
Physical singleturn resolution
- 1).
If the scaling function is enabled (see the bit 2
- 1.
WARNING
operation every time you set a new
values (
6001-00 Measuring units per revolution
).
6004-00 Position value
[Unsigned32, ro]
This object contains the current position value of the encoder.
The output value is scaled according to the scaling parameters (if the scaling
function is enabled), see the bit 2
object.
The position value is transmitted cyclically or synchronously according to the
settings in the
1800 TPDO communication parameter 1
1802 TPDO communication parameter 3
objects (see on page 48 ff).
WARNING
Please note that the position value issued by the encoder is expressed in pulses;
thus you have then to convert the number of pulses into a linear measuring
unit.
MAN SFA_5000_10000_CB E 1.0.odt
6 - CANopen® interface
67 of 88