L'HOTELLIER
COMPONENT MAINTENANCE MANUAL
12589-( )
PRINTED IN FRANCE
26-20-50
Page 7009
APR 01/11
N.
Close valves A, B, and E.
NOTE :
The cooling bath/coil is not necessary to do the fill procedure if the halon supply-
cylinder is pressurized.
NOTE :
The cooling coil keeps 0.50 to 0.70 lb (0.23 to 0.32 kg) of CBrF
3
. Allowance must be
made for this so that the container will not weigh too much after it is pressurized with
nitrogen.
O.
Remove the coil from the cooling solution.
P.
After the container pressure and temperature become stable, open valves C and F.
CAUTION : VALUES IN THE TABLE DO NOT INCLUDE THE CHARGING GAUGE TOLERANCES.
Q.
Adjust the regulator to the necessary pressure for the ambient temperature given in Table 7002
Table 7002
Pressure -Temperature Properties
Ambient Temperature °C
Container Pressure KPa
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
3600
3650
3700
3800
3900
3950
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
R.
Add nitrogen pressure to the container as follows:
(1)
Open valve E and monitor the fill-pressure gauge and the supply-pressure gauge until the
two pressures are equal.
(2)
Close valve E. Lift and shake the container to cause the nitrogen to be absorbed into the
CBrF
3
.