L'HOTELLIER
COMPONENT MAINTENANCE MANUAL
12589-( )
PRINTED IN FRANCE
26-20-50
Page 5006
APR 01/11
Table 5002 - Acceptance certificate
Results
CUSTOMER ACCEPTATION:
(éventuelle
Halon 1301
Observation
INSPECTION OF THE SAMPLING
CONTROL
Serial number
control report N°
date of report
CMM26-20-50
ACCEPTANCE CONDITION :
- 40° à + 100°C
42 bar +/- 1
Non leak
Admissible leak Q<1g/an
PERFORMED INSPECTION
Welded reservoir X-ray inspection
expected value
CONTROL
Conformity
Correct manufacturing. Correct dimensions.
Correct appearance
REFERENCE :
Extinguisher agent type :
12589-01
Pressure at 20 °C :
Control stamp présence
143 bar during 30 sec. minimum
Déformation < 10% de l'VE
SERIAL NUMBER :
0,046 kg
Theoretical nitrogen weight :
PVR EXT
N°
____________ (lot)
CARACTERISTIQUES :
MFG:
IDENTIFICATION:
AMENDEMENT:
Extinguisher agent weight :
1,200 kg 0/+0,045kg
EXTINGUISHER
date of report
Lot N°
Date + sig Stamp :
Name:
Date + sig Stamp :
Temp. of functioning :
Conformity (finished extinguisher)
Watertightness
Observations :
Main disc
General conditions
LAUNCHING FILE N° :
Reservoir test pressure
INSPECTION OF THE
SECONDARY LOT OF
FABRICATION
Pressure control
Safety relief valve
CONTROL
control report N°
L'HOTELLIER CONTROL:
Functional test
Name:
Weighing inspection
± 10 g full weight indicated on the marking
± 60 g weight indicated on the drawing
4, Rue Henri Poincaré
92 167 ANTONY Cedex - France
Tel: +33. (0)1. 46. 66. 08. 08.
Fax: +33. (0)1. 46. 66. 23. 24.
The document reference is online, please check the correspondence between the online documentation and the printed version.