Chapter 8 Exercising program
8-38
3) Communication protocol of temperature controller
For communication between Cnet I/F module and temperature controller, communication type of temperature
controller is to be informed of. The example describes how to prepare program supposing that communication
protocol is as shown in [Figure 8.20].
[Figure 8.20] Communication protocol of temperature controller
A) Write request frame(Cnet’s request : Write data of 12 channels in temperature controller)
Classification
Header
Device ID
Command
Address
Channel
number
Data
Frame
[DLE][STX]
01
01
30
0c
12-word data
BCC calculation range
BCC
Tail
[DLE][ETX]
B) Read request frame(Cnet’s request : Read temperature value of 12 channels in temperature controller)
Classification
Header
Device
ID
Command
Address
Channel
number
BCC
Tail
Frame
[DLE][STX]
01
02
80
0c
[DLE][ETX]
BCC calculation range
GLOFA Cnet
User defined master
Temperature controller
Slave station
A) Write request frame
C) Response frame
B) Read request frame