Chapter 8 Exercising program
8-3
Item
Setting contents
Remark
Communication speed
9600 BPS
Identical to Cnet I/F module
Data type
Asynchronous 10 bits
Data-8bits/Start-1bit/Stop-1bit
RTS-CTS delay
0 msec
Set to the smallest value
DTR control
Forced ON
Comm mode
4-line type
As agreed with the dedicated line spec.
3) Setting of basic parameters
Mode and basic parameters need setting for TM master slave communication. [Table 8.2] describes setting
items for this. For dedicated modem communication, apply setting to RS-232C channel.
[Table 8.2] Setting items
Setting item
TM master module
TM slave module
Remark
Module name
G3L-CUEA
G4L-CUEA
Channel mode
Stand-alone mode
Stand-alone mode
Operation mode
[Note1]
‘3’ : dedicated mode Ver.2.0
‘3’ : dedicated mode
RS-232C station No.
Basic value(Not used)
0 ~ 7 station available
RS-232C
communication type
Dedicated modem
RS-232C
communication speed
9600 BPS/DATA 8 bits/START 1 bit/STOP 1 bit
RS-232C
channel setting
only valid
Remark
[Note1] Cnet I/F module in TM master side shall be of Ver.2.0 or later as is in dedicated master mode to
communicate. TM slave side as used in dedicated mode slave is available regardless of the version.
Next is setting screen of Frame Editor to be set as in [Table 8.2].