Chapter 7 Communication function
7-19
(3)
Registration of Immediate response frame: Immediate response frame of the structure as in [Table 7.8] is
registered according to the sequence below.
①
Select the 3
rd
item of frame list in Frame Editor and input the identical ‘IMM_RESPONSE’ with the
input name as an immediate response frame when setting the received frame in frame name. And then
select SEND in TX/RX and input data below to Header. Next is the input result.
②
Input segment : Since frame body of [Table 7.8] is composed of CONST only, set it to CONST and
input ‘RD24’. As it is ASCII transmission, select ASCII. Next is the input result of segment.
[Note]
.
Remark
[Note 1] In immediate response frame, ARRAY type of segment can’t be used.
③
Input [ETX] to Tail as below. As [BCC] is not applied, no setting is needed.
④
[Figure7.9] shows registration screen of the immediate response frame. Immediate response frame
as registered with an identical name of immediate response frame in receiving frame differently from
other transmission frames, needs no preparing of additional transmission program in GMWIN
program. Immediate response frame, if frame set to ‘RD_DATA’ is received, searches for
‘IMM_RESPONSE’ frame set to immediate response frame and transmits the frame in specified
format automatically in Cnet I/F module.