Chapter 7 Communication function
7-110
7.4.2 Operating mode & downloading of communication driver
1)
Type of communication drivers
Other company’s dedicated mode can be set by mode change from On-line mode of mode switch ‘9’ via Frame
Editor to other company’s dedicated mode, and can be operated via AB Asynchronous Link Full Duplexor
MODBUS protocol by downloading of communication driver file to Cnet I/F module. Communication driver file as
an OS file to perform operation of specified protocol among other company’s dedicated modes is to download just
one Cnet I/F module for the service. Communication driver is saved in Cnet I/F module’s built-in flash memory as
kept even if powered OFF. Communication drivers are classified as specified in Table 7.26] according to protocol
type and Cnet I/F module type with extension name of *.LIB.
[Table 7.26] Type of communication drivers
File name
Description
Applicable module
AB34.LIB G3L-CUEA/G4L-CUEA
AB6.LIB
AB Asynchronous Link Full Duplex communication driver
G6L-CUEB/G6L-CUEC
MODBUS34.LIB G3L-CUEA/G4L-CUEA
MODBUS6.LIB
MODBUS ASCII/RTU communication driver
G6L-CUEB/G6L-CUEC
Communication driver file agreed with the service shall be downloaded, however, the number of downloads is not
restricted. In other words, a module used in AB Asynchronous Link Full Duplex can be used in MODBUS
communication mode if MODBUS communication driver has been downloaded.
2)
How to download communication driver
Correspondent communication driver file is to be downloaded for the service in other company’s dedicated mode
as selected among the files in [Table 7.26]. If incorrect file is selected and downloaded, normal operation of Cnet
I/F module isn’t allowed. Next is how to download other company’s communication driver via Cnet I/F module.
A) If Cnet mode switch is set to Write flash mode and then PLC is powered on, LED No.‘0’ of Cnet I/F module