Chapter 7 Communication function
7-57
4)
Example of use
When the STATUS of PLC with station No.1 is read.
(Computer request format)
Format
Name
Header
Station No.
Command
Command type
Tail
Frame
check
frame(Ex.)
ENQ H01 R(r) ST EOT BCC
ASCII value
H05 H3031
H52(72)
H5354 H04
(For PLC ACK response after execution of command)
Format
Name
Header
Station No.
Command
Command
type
STATUS
data
Tail
Frame
check
frame(Ex.)
ACK
H01
R(r)
ST
See STATUS FORMAT
ETX
BCC
ASCII value
H06
H3031
H52(72)
H5354
H03
(For PLC NAK response after execution of command)
Format
Name
Header
Station No.
Command
Command
type
Error code
Tail
Frame
check
Frame(Ex.) NAK H01 R(r)
ST
Error
code(2)
ETX BCC
ASCII value
H15
H3031
H52(72)
H5354
Error code(4)
H03
Содержание GLOFA-GM Series