Chapter 7 Communication function
7-33
B) Error codes (status of Function Block)
Code
Error type
Meaning
06
Slave Device Busy
During TX//RX or Waiting for receiving
09 Parameter
Error
Setting error of communication parameters or Setting error of link
permission
10
Frame Type Error
Frame is not in transmission or not set.
C) Error flag
①
Errors related with frame list
9
Saved to _UD_ERR[n].
Bit No.
Error type
Meaning
Remark
Bit 0
Frame Length Over
Error occurs if frame is over 128 byte(HEX : 256 byte)
Bit 1
Device Area Over
Error occurs if I/Q area(128 byte) or M area is exceeded
Bit 2
BCC Setting Error
BCC setting error
Error flag on
transmission
side
Bit 8
BCC Check Error
If received BCC value is incorrect
Bit 9
Mismatch Error
If received frame isn’t agreed with registered frame
Bit 10
HEX Change Error
Error occurs on HEX converting
Bit 11
Frame List Error
Frame setting error or link permission setting error