Chapter 7 Communication function
7-60
9
Error code is HEX and 2 bytes(ASCII code, 4 bytes), which indicates type of error. For the details, see
Appendix ‘B. Error Code Table’.
4) Example of use
In case “HFF” is written in %MW230 address of station No.1.
(Computer request format)
Format
Name
Header
Station
No.
Command
Command
type
Number
of blocks
Variable name
length
Variable
name
data
Tail
Frame
check
Frame (Ex.)
ENQ
H01
W(w)
SS
H01
H06
%MW230
H00FF EOT BCC
ASCII
value H05 H3031 H57(77) H5353
H3031
H3036
H254D5732
3330
H30304646 H04
(For PLC ACK response after execution of command)
Format
Name
Header
Station No.
Command
Command type
Tail
Frame
check
Frame (Ex.)
ACK
H01
W(w)
SS
ETX
BCC
ASCII
value
H06 H3031 H57(77) H5353 H03
(For PLC NAK response after execution of command)
Format
Name
Header
Station No.
Command
Command type
Error code
Tail
Frame
check
Frame (Ex.)
NAK
H01
W(w)
SS
Error code(2)
ETX
BCC
ASCII value
H15
H3031
H57(77)
H5353
Error code(4)
H03
Содержание GLOFA-GM Series
Страница 355: ...Appendix A 12 A 3 Dimensions of appearance G3L CUEA Unit mm 118 0 130 5 35 0 250 0 ...
Страница 356: ...Appendix A 13 G4L CUEA 107 0 121 5 35 0 135 0 ...
Страница 357: ...Appendix A 14 G6L CUEB G6L CUEC Dimensions of G6L CUEB G6L CUEC are identical with each other 81 1 90 0 35 0 110 0 ...