Chapter 6 System configuration
6-1
Chapter 6 System configuration
Various communication systems can be configured via this module in accordance with application fields. This chapter
describes examples of
system configurations which are available or unavailable for the application fields.
6.1 System configuration available
6.1.1 1:1 Connection (no modem) to PC
PC and Cnet are connected via RS-232C or RS-422 channel in 1:1 connection system with PC or PLC not
through modem. Most PCs are operated as master stations and Cnet I/F modules are operated as slave stations
that respond the request of PC. Since no modem is applied, communication distance is max.15m via RS-232C
channel and max.500m via RS-422 channel. Operation mode of Cnet I/F module shall be set as agreed with
communication type of PC.
[Figure 6.1] 1:1 communication system with PC
Module setting
Type
RS-232C
RS-422
Channel mode
Station No.
Dedicated mode
Dedicated mode
GLOFA PLC Cnet
Other company’s
dedicated mode
Other company’s
dedicated mode
Stand-alone
channel
0 ~ 31
MMI S/W
GLOFA-PLC
RS-232C/RS-422
Interface