Test Run
Installation Manual
71
ENGLISH
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-seg-
ment LED of outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
2) Outdoor Unit
Error No.
Error Type
Main Reasons
Outdoor unit related error (CH)
2
1
1
Inverter compressor IPM defect
Inverter compressor drive IPM defect /
inverter compressor defect
2
2
1
Inverter compressor over current
Increase of inverter compressor CT value
2
3
1
Inverter compressor DC Link low
voltage
After inverter activation relay is ON, DC
voltage recharge defect
2
4
1
Outdoor Unit High Pressure Switch
System is turned off by outdoor unit high
pressure switch.
2
5
1
High/low Inverter input voltage
Inverter input voltage exceeds the unit limit
and lasts for 4 s (173V ~ 289V)
2
6
1
Inverter compressor activation
failure
Inverter compressor error, causing initial
activation failure
2
7
1
Inverter PSC/PFC Fault Error
Error by overcurrent at inverter input
2
8
1
Inverter DC Link high voltage error
Inverter DC voltage recharge, causing
compressor OFF
2
9
1
Inverter compressor overcurrent
Inverter compressor activation failure or
increase of CT value
3
2
1
Excessive rise of inverter compres-
sor discharge temperature
Excessive rise of inverter compressor dis-
charge temperature, causing compressor
OFF
3
4
1
Excessive rise of high pressure of
inverter compressor
Excessive rise of high pressure of inverter
compressor, causing compressor OFF
3
5
1
Excessive drop of low pressure of
inverter compressor
Excessive drop of low pressure of inverter
compressor, causing compressor OFF
3
6
1
Low pressure ratio error of inverter
compressor
High pressure/low pressure ratio of inverter
compressor is maintained at below 1.8 for 3
min. or more
4
0
1
Inverter compresso’r CT sensor defect Inverter compressor CT sensor defect
4
1
1
Inverter compressor discharge pipe
temperature sensor defect
Inverter compressor discharge temperature
sensor disconnection or short circuit
4
2
1
Low pressure sensor defect of
inverter compressor
Low pressure sensor disconnection or short
circuit of inverter compressor
4
3
1
High pressure sensor defect of
inverter compressor
High pressure sensor disconnection or short
circuit of inverter compressor
4
4
1
Inverter inside air temperature
sensor defect
Inverter inside air temperature sensor
disconnection or short circuit
4
5
1
Outdoor Unit Heat Exchanger
Temperature Sensor Fault
Outdoor Unit Heat Exchanger Temperature
Sensor Open or Short