Test Run
Installation Manual
69
ENGLISH
• This function displays the disorder types at the self diagnostics and the occurrence of the dis-
order for the product.
• The disorder display shows the code in the following table on the red/green LED of the wired
remote controller and outdoor unit control board.
• If two or more types of disorders occur simultaneously, it displays in the order of the error
number.
• After error occurs, the error code disappears when the disorder is repaired.
h
Error code 01, 08, 17, 18 can be operated with emergency operation.
Troubleshooting
Error No.
Error Type
Main Reasons
CH01
Air temperature sensor error
Air temperature sensor disconnection or short circuit
CH03
No communication between wired remote
controller & indoor unit
The remote controller does not receive the signal from
indoor unit during specific time
CH05
Indoor unit & outdoor unit communication
error
No signal communication between indoor unit & out-
door unit
CH08
Water tank temperature sensor error
Water tank temperature sensor disconnection or short
circuit
CH09
Indoor unit EEPROM error
Communication between the micro-processor & the
EEPROM / Error due to EEPROM damage
CH11
Indoor unit & inverter PCB communication
error
No signal communication between indoor unit & in-
verter PCB
CH14
Flow switch error
Abnormal working of flow switch
CH15
Water pipe overheated
Water outlet temperature is above 90℃
CH16
Water inlet & outlet temperature sensor
error
Water inlet & outlet temperature sensor disconnection
or short circuit simultaneously
CH17
Water inlet temperature sensor error
Water inlet temperature sensor disconnection or short
circuit
CH18
Water outlet temperature sensor error
Water outlet temperature sensor disconnection or short
circuit