Position value submenu
Note!
The parameters mentioned in the "Position value", "I/O" and "Other" submenus must be set
via the GSDML file of the AMS 348
i
. For test purposes, the parameters can be changed
directly on the AMS 348
i
via the display structure described below. After deactivation of the
parameter enable, however, the parameters stored in the GSDML file continue to be valid.
The parameters changed directly on the AMS 348
i
for test purposes are overwritten again.
I/O submenu
Table 8.3:
Position value submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Unit
Metric/Inch
Specifies the units of the measured distances
Metric
Counting
direction
Positive/Negative
Positive: The measurement value begins at 0 and increases
with increasing distance.
Negative: The measurement value begins at 0 and decreases
with increasing distance. Negative distance values may need
to be compensated with an offset or preset.
Positive
Offset
Output value = measurement value + offset
The resolution of the offset value is independent of the
selected "Position resolution" and is entered in mm or inch/
100. The offset value is effective immediately after entry. If the
preset value is activated, this has priority over the offset. Pre
-
set and offset are not offset against each other.
0 mm
Preset
The preset value is accepted by means of teach pulse. The
teach pulse can be applied to a hardware input of the M12
PWR connector. The hardware input must be appropriately
configured. See also configuration of the I/Os.
0 mm
Free resolu
-
tion value
The measurement value can be resolved in increments of 1/
1000 within the 5 … 50000 value range. If e.g. a resolution of
0.875mm per digit is required, the parameter is set to 875.
1000
Error delay
ON/OFF
Specifies whether, in the event of an error, the position value
immediately outputs the value of the "Position value in the
case of failure" parameter or the last valid position value for
the configured error delay time.
ON/100
ms
Position value
in the case of
failure
Last valid value / zero
Specifies which position value is output after the error delay
time elapses.
Zero
Table 8.4:
I/O submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
I/O 1
Port con
-
figuration
Input/Output
Defines whether I/O 1 functions as an output or input.
Output
Switching
input
Function No function/teach preset/laser ON/OFF
No function