EtherCAT interface
Leuze electronic GmbH + Co. KG
AMS 338
i
73
TNT
35/7-2
4V
Object 2050
h
Configuration of I/O 1
The settings in "bold" are the default settings.
Bit 0: Function of I/O 1 connection on PWR M12
0 = Input
1 = Output
Bit 1: activation
If I/O 1 is defined as input (see bit 0):
0 = 1 - 0 transition
1 = 0 - 1 transition
If I/O 1 is defined as output (see bit 0):
0 = low active (the output is set to 0 if the event occurs)
1 = high active (the output is set to 1 if the event occurs)
Bit 2 - Bit 7: Reserve
0 = Reserve
1 = NC
Note!
Bit 8 to bit 23 affect the "OR" linked output.
Bit 8: Position limit value 1
If the position value is outside of configured limit value 1, the output is set.
0 = OFF
1 = ON
Bit 9: Position limit value 2
If the position value is outside of configured limit value 2, the output is set.
0 = OFF
1 = ON
Bit 10: Velocity limit value
If the velocity value is outside of the configured values, the output is set. The monitoring
processes from objects 2021h to 2025h are "OR" linked to this bit.
0 = OFF
1 = ON
Index
Sub-
index
Name
Data type
Access
Value range
Comment
(hex)
(hex)
Minimum
Maximum
Default
2050
--
I/O1
u 32
rw
--
--
--
See below