EtherCAT interface
64
AMS 338
i
Leuze electronic GmbH + Co. KG
Object 2001
h
Static preset value
The static preset value is a parameter that is no longer changed after the system has been
handed over to the end operating company. It is configured during commissioning and then
remains unchanged.
A preset value can be entered in the object. The preset value is activated by "preset teach"
and deactivated with "preset reset". After preset teach, the current position value is offset
against the configured preset value. After preset reset, the original measurement value is
displayed.
Object 2002
h
Dynamic preset value
The dynamic preset value can be adapted permanently by the control.
The dynamic preset value is activated by "preset teach" and deactivated with "preset reset".
After preset teach, the current position value is offset against the configured preset value.
After preset reset, the original measurement value is displayed.
Index
Sub-
index
Name
Data type
Access
Value range
Comment
(hex)
(hex)
Minimum
Maximum
Default
2001
01
Preset
value
static
int 32
rw
-999999
999999
0
Preset value in
mm or
in/100 depend
-
ing on selected
unit
02
Preset
settings
u 8
rw
0
2
0
Value 1 =
Preset teach
Value 2 =
Preset reset
Index
Sub-
index
Name
Data type
Access
Value range
Comment
(hex)
(hex)
Minimum
Maximum
Default
2002
01
Preset
value
static
int 32
rw
-999999
999999
0
Preset value in
mm or
in/100 depend
-
ing on selected
unit
02
Preset
settings
u 8
rw
0
2
0
Value 1 =
Preset teach
Value 2 =
Preset reset