3.0 Installation
3.1 Environmental
Requirements
Maximum operating temperature:
125°F (52°C)
Minimum operating temperature:
32°F (0°C)
Operating humidity range:
30% to 90% RH, non-condensing
Maximum storage temperature:
158°F (70°C)
Minimum storage temperature:
-4°F (-20°C)
Storage humidity range:
10% to 90% RH, non-condensing
Heat generated under normal operation: 34.1 BTU/hour
The ConsoleServer 800 uses convection cooling to dissipate the majority of its
excess heat. Be careful not to block the air vents on the sides of the unit. If
mounted in an enclosed rack, it is recommended that the rack have a ventilation
fan to provide adequate airflow through the unit.
3.2 Physical
Installation
The ConsoleServer 800 may be installed either in an EIA-standard 19 inch rack
or as a desktop unit. If the unit is used as a desktop unit, then four rubber feet
(included) should be applied to the underside of the unit to prevent scratching of
the desk surface.
Rack Mount Instructions:
Materials Required:
•
ConsoleServer
800
•
EIA-standard 19 inch rack
•
screws to fit rack
•
screwdriver
1.
Choose the mounting location for the ConsoleServer. Avoid placing the
ConsoleServer in a location where its side vents will be blocked, or where
the ConsoleServer would block another unit’s ventilation holes.
2.
Slide the unit between the rack uprights and align the mounting holes. It
may be helpful to have two people for this step and the next one.