TITAN
113
EN
cod. 3541Z410 - Rev 01 - 09/2022
A
To exit the TEST mode, only use the
"Stop Test" contextual button
.
fig. 83
The TEST mode is automatically disabled in any case after 15 minutes.
DO NOT TURN OFF THE BOILER ELECTRICALLY DURING THE TEST.
Otherwise, when the power is switched on again, the system starts to work as if still in
TEST
mode and not
like for a normal heating request.
Check of simultaneous activation of all modules
Within the
Test Mode
menu screen, select TEST (See
fig. 84). Press
fig. 84
Using
contextual button 2
immediately bring the va-
lue
(-)
, to
0%
PREVENT THE BOILER FROM IMMEDIATELY OPE-
RATING AT MAXIMUM POWER.
INCREASE THE POWER SLOWLY TO AVOID
THERMAL SHOCK.
Reach the value of 100% power in a time of 2-3 minu-
tes.
fig. 85
With all modules on at the same power (maximum or minimum), combustion can be checked at the boiler flue outlet.
per salvare Potenza
Modalità Test
Stop Test
1:
50% 80%
per confermare
Modalità Test Cascata
1
2
TEST
Modalità Test Cascata
Stop Test
4/8
13%