TITAN
87
EN
cod. 3541Z410 - Rev 01 - 09/2022
If the room temperature is lower than the desired value, it is advisable to set a higher order curve and vice versa. Pro-
ceed by increasing or decreasing in steps of one and check the result in the room.
fig. 31- Compensation curves
fig. 32- Example of compensation parallel curve offset
A
This parameter is used only if the time programming has been activated. See ”Time programming” on page 82
Outside Temperature Heating OFF
Access the “Out Temp Heat Off” to activate the function: between 7°C and 30°C.
If activated, this function will deactivate the heating demand whenever the temperature measured by the external probe
is higher than the programmed value.
The heating demand will be reactivated as soon as the temperature measured by the external probe is lower than the
programmed value.
Adjustments from remote timer control
A
If the boiler is connected to the Remote Timer Control (optional), the previously described adjustments are
managed as described in table 1.
Table 1
20
30
40
50
60
70
80
90
85
20
10
0
-10
-20
1
2
3
4
5
6
8
9
10
7
20
30
40
50
60
70
80
90
85
20
30
40
50
60
70
80
90
85
1
2
3
4
5
6
8
9
10
7
1
2
3
4
5
6
8
9
10
7
OFFSET = 20
OFFSET = 60
Heating temperature adjustment
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
DHW temperature adjustment (with
optional hot water tank installed)
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer/Winter Switchover
Summer mode has priority over a possible Remote Timer Control heating request.
Eco/Comfort selection
(with optional
hot water tank installed)
On disabling DHW from the Remote Timer Control menu, the boiler selects Economy mode.
In this condition, the button detail 10 - fig. 1 on the boiler panel, is disabled.
By enabling DHW from the Remote Timer Control menu, the boiler selects Comfort mode. In
this condition, use the button detail 10 - fig. 1 on the boiler panel to select one of the two
modes.
Sliding Temperature
Both the Remote Timer Control and the boiler card manage the Sliding Temperature adjust-
ment: between the two, the Sliding Temperature of the boiler card has priority.