Parameters Menu - Transparent Parameters
31 parameters are available, indicated by the letter
“P”
, which are not modifiable from Remote Timer Control.
Table 5-Parameters - Transparent
Notes
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter
given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is mo-
dified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
Parameter
Description
Range
P01
Ignition power
0-100%
30
P02
Heating ramp
1-10°C/minute
1
P03
Virtual setpoint min. temperature
20 ÷ 80°C
20
P04
Heating standby time
0 ÷ 10 minutes
4
P05
Heating Post-Circulation
0 ÷ 255 minutes
3
P06
Pump operation
0-3 Operation strategy
0
P07
Modulating pump min. speed
0 ÷ 100%
30
P08
Modulating pump start speed
0 ÷ 100%
75
P09
Modulating pump max. speed
30 ÷ 100%
100
P10
Pump deactivation temperature during Post-Circulation
0 ÷ 100°C
35
P11
Pump activation hysteresis temperature during Post-Circulation
0 ÷ 20°C
5
P12
Heating user min. setpoint
10 ÷ 90 °C
20
P13
Heating user max. setpoint
20 ÷ 90 °C
80
P14
Max. output in heating
0-100%
80
P15
DHW ramp
1-10°C/min
5
P16
DHW standby time
0-255 seconds
120
P17
DHW pump Post-Circulation
0-255 seconds
30
P18
With B02 = 7 - Not implemented
--
--
With B02 = 8 - DHW user min. setpoint
10° ÷ 40°
10°
With B02 = 9 - DHW user min. setpoint
10° ÷ 40°
10°
P19
With B02 = 7 - Not implemented
--
--
With B02 = 8 - DHW user max. setpoint
40° ÷ 70°
65°
With B02 = 9 - DHW user max. setpoint
40° ÷ 70°
65°
P20
Max. output in DHW
0-100%
80%
P21
With B02 = 7 - Not implemented
--
--
With B02 = 8 - Hot water tank hysteresis
0° ÷ 60°
2°
With B02 = 9 - Hot water tank hysteresis
0° ÷ 60°
2°
P22
With B02 = 7 - Not implemented
--
--
With B02 = 8 - Primary setpoint
70° ÷ 85°
80°
With B02 = 9 - Primary setpoint
70° ÷ 85°
80°
P23
With B02 = 7 - Not implemented
--
--
With B02 = 8 - Legionella protection
ON - OFF
OFF
With B02 = 9 - Legionella protection
ON - OFF
OFF
P24
Fan frequency in standby mode
0-255 Hz
0
P25
Modulating pump adjustment temperature
0-60°C
20
P26
Primary exchanger protection temperature
0-80°C
35
P27
System min. pressure value
--
--
P28
System nominal pressure value
--
--
P29
Exchanger protection intervention
0
= No F43,
1-15
= 1-15°C/second
0
P30
Heating hysteresis after ignition
6-30°C
10
P31
Timer for heating hysteresis after ignition
0-180 seconds
60