TITAN
92
EN
cod. 3541Z410 - Rev 01 - 09/2022
B
Also, a filter must be installed on the system return piping to prevent impurities or
sludge from the system clogging and damaging the heat generators.
The filter must be installed when replacing generators in existing systems. The ma-
nufacturer declines any liability for damage caused to the generator by failure to
install or inadequate installation of this filter.
Make the connections to the corresponding connections according to the drawing in fig. 38.
fig. 38
Table 2- SIZE OF CONNECTIONS
System water characteristics
Before installing the TITAN generator, the new or existing system must be properly cleaned in order to eliminate insta-
llation residues, solvents, sludge and contaminants in general that may compromise the effectiveness of the protective
conditioning treatments. Use neutral cleaning products that do not attack metals, rubber and plastic parts of the gene-
rator/system. Empty, wash and recharge the system in compliance with the following instructions. A dirty system will not
guarantee the life of the generator over time, even with the use of protective conditioners.
B
TITAN
boilers are suitable for installation in heating systems with non-significant
entry of oxygen (ref. systems
"case I”
EN14868). A physical separator (e.g. plate
heat exchanger) must be provided in systems with continuous entry of oxygen (e.g.
underfloor systems without anti-diffusion pipes or open vessel), or frequent (fre-
quent water replenishment).
The water in a heating system must be treated in compliance with the laws and re-
gulations in force, have the characteristics required by UNI 8065, and comply with
the provisions of EN14868 (protection of metallic materials against corrosion).
7
10
11
a4
10
- System flow
DN65
flanged
11
- System return
DN65
flanged
7
- Gas inlet
DN40
flanged
a4
- Flue connection
ØPR 15000