5.1 Technical data table
The column on the right gives the abbreviation used on the data plate.
5.2 Diagrams
Pressure loss
fig. 5 - Pressure loss
Data
Unit
ECO - LOGIK 3
ECO - LOGIK 4
ECO - LOGIK 5
ECO - LOGIK 6
ECO - LOGIK 7
Heat output Wood
kW
19
27
36
43
50
(P)
Heat output Coke
kW
22.5
32.5
42.5
52.5
62.5
(P)
Heat output Pellets
kW
22
30
36
42
48
(P)
Efficiency Wood
%
77
78
78
78
78.5
Efficiency Coke
%
79
79.5
80
80.5
81
Efficiency Pellets
%
88.48
88.66
88.7
89.02
89.3
Max. working pressure
bar.
4
4
4
4
4
Water content
L.
26
30
34
38
42
Chamber volume
dm
3
48
68
88
108
128
Loading opening dimensions Wood/Coke
mm
384x210
384x210
384x210
384x210
384x210
Temperature adjustment range Wood/Coke
°C
30-90
30-90
30-90
30-90
30-90
Max. heating temperature Wood/Coke
°C
95
95
95
95
95
Recommended temperature setting
°C
>60
>60
>60
>60
>60
Boiler return min. temperature
°C
50
50
50
50
50
Safety coil cooling
water supply line requirements
Min. pressure
- bar
2.0
2.0
2.0
2.0
2.0
Min. flow rate
- l/min
10
10
10
10
10
Max. temperature
- °C
25
25
25
25
25
Duration of one wood load
h
2.5
2.5
2.5
2.5
2.5
Duration of one coke load
h
4.5
4.5
4.5
4.5
4.5
Min. flue draught Wood
Pa
12
14
16
18
20
Min. flue draught Coke
Pa
8
10
15
20
25
Min. flue draught Pellets
Pa
23
25
28
30
32
Efficiency class EN303-5 - WOOD
3
3
3
3
3
Efficiency class EN303-5 - PELLETS
5
5
5
5
5
Efficiency class EN303-5 - PELLETS
5
5
5
5
5
Empty weight
kg
193
241
289
337
385
14
12
10
8
6
4
2
0
mbar
0
500
lt/h
1000
1500
1500
2000
2500
3000
3500
4000