1.3 

Commonwealth of Massachusetts Requirements 

The following requirements reference various Massachusetts and national codes not contained in this manual. 

For all sidewall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for 
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is 
less than (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following require-
ments shall be satisfied:    

1.3.1 

Installation of Carbon Monoxide Detectors 

At time of installation of side wall horizontally vented gas fueled equipment, the installing plumber or gas-fitter shall observe that a hard wired 
carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addi-
tion, the installing plumber or gas-fitter shall observe that a battery operated or hard wired carbon monoxide detector is installed on each addi-
tional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of 
the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.    

 

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or attic, the hard wired carbon monoxide 
detector with alarm and battery back-up may be installed on the next adjacent floor level.   

 

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of 
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed.   

1.3.2 

Approved Carbon Monoxide Detectors 

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed 
and IAS certified. 

1.3.3 

Signage 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum of eight (8) feet above grade 
directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print 
no less the one-half inch (1/2) in size, 

 “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

  

1.3.4 

Inspection 

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon in-
spection ,the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08 (2) (a) 1 
through 4. 

1.3.5 

Exemptions 

The following equipment is exempt from 248 CMR 5.08 (2) (a) 1 through 4:The equipment listed in Chapter 10 entitled “Equipment Not Re-
quired To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and Product Approved side wall horizontally vented gas 
fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part  for residential pur-
poses.   

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system 

components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall 

include: 

 

 

 

Detailed instructions for the installation of the venting system design or the venting system components; and 

 

 

A complete parts list for the venting system design or venting system. 

When the manufacturer of Product Approved side wall horizontally vented gas equipment does not provide the parts for venting the flue gases, 

but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer: 

 

 

The referenced “special venting systems” instructions shall be included with the appliance or equipment installation instructions and;   

 

 

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

 

detailed installation instructions. 

 

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all 

parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at  the completion of the 

installation.

 

Gas Equipment Venting System Provided 

Gas Equipment Venting System Not Provided 

1.3.6 

Manufacturer Requirements 

Содержание Slayton 42S

Страница 1: ...anual with the appliance CONSUMER Retain this manual for future reference This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not proh...

Страница 2: ...e line of gas and wood fireplaces unique cabinets and stylish accessories to complement any d cor Adding a fireplace is one of the best ways to increase the value of your home and we are proud to offe...

Страница 3: ...32 14 0 CONTROL SYSTEM COMPONENTS 33 14 1 Remote Control 33 14 2 Gas Valve 33 14 3 Pilot Assembly 33 15 0 SYSTEM OPERATION 34 15 1 Prepare Components 34 15 2 Initialize the Control System for the Fir...

Страница 4: ...ren and other at risk individuals out of the room and away from hot surfaces Clothing or other flammable material should not be placed on or near the appliance Adequate accessibility clearances for se...

Страница 5: ...of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print no less the one half inc...

Страница 6: ...ower Assembly SL42 HHSS Vent Heat Shield Assembly AL36 DRAM Rock Driftwood Accent Media SL42 500 Driftwood Log Set SL42 RAM Rock Accent Media 970 Heat Duct Kit Heat Duct Kit Natural Gas LP Gas Minimum...

Страница 7: ...f fireplace and all components Refer to 18 0 Finalizing the Installation on page 42 NOTE The qualified installer should follow the procedure best suited for the installation 2 5 Installation Overview...

Страница 8: ...illimeters 827 1271 1271 402 1154 494 146 252 Table 2 2 Appliance Clearances Top of appliance stand offs to framing 0 in 0 mm From appliance left side right side stand offs 0 in 0 mm From appliance ba...

Страница 9: ...ng the secondary stand off heat shield and the top stand off brackets located on the top of the fireplace 2 Form the top stand off brackets as shown then re attach to the fireplace using screws previo...

Страница 10: ...fireplace face Do not bend toward fireplace face 4 Position framing stud against stand off located on the backside of nailing flange Secure with nails or screws NOTE Depending on facing material tabs...

Страница 11: ...ional 970 Heat Duct Kit refer to 12 0 970 Heat Duct Kit on page 26 19 in 483 mm represents the minimum distance from the front of the fireplace to back wall of framing This is the minimum wall depth r...

Страница 12: ...of the fireplace must be level with finished hearth Build the hearth to desired size and height If a hearth extension is desired combustible material may be used Above floor level installations A sol...

Страница 13: ...ption of the header 5 0 MANTEL REQUIREMENTS Figure 5 1 Mantel Projections and Non Combustible Zone NOTE If you plan to mount a television above the fireplace please refer to 7 0 Recess Construction on...

Страница 14: ...fireplace must be installed for every type of venting configuration Refer to 11 5 Vent Heat Shield Assembly Installation on page 21 6 0 TYPICAL INSTALLATION OPTIONS 6 1 Horizontal Installation 6 2 Ve...

Страница 15: ...above a heat source Television location rests solely on the homeowner Hussong Manufacturing shall not be held liable for any adverse effects that may be caused by heat on a TV located near a Kozy Heat...

Страница 16: ...nd this point The glass frame assembly must be removable Non combustible material is required at the top and the sides of the fireplace Figure 8 3 reflects these dimensions Do not secure material to l...

Страница 17: ...allation must be done by a licensed plumber or gas fitter NOTE A listed and Commonwealth of Massachusetts approved 1 2 in 13 mm tee handle manual shut off valve and flexible gas connector are to be co...

Страница 18: ...onents will not function on battery back up power 10 0 WIRING SCHEMATICS Figure 10 1 IFC Control Module Wiring IFC Control Module 1 5 V type AA 1 5 V type AA 1 5 V type AA 1 5 V type AA Flame Sensor S...

Страница 19: ...X X Simpson Dura Vent DV PRO 8 x 5 Direct Vent Systems X X 11 0 VENTING 11 1 Approved Vent Systems 11 2 Restrictor Assembly Installation Slide restrictor into exhaust pipe on top of fireplace with tab...

Страница 20: ...nimum Horizontal Vent Pipe Length Maximum Horizontal Run 9 in 6 in 229 mm 152 mm 9 in 229 mm 12 ft 3 66 m Figure 11 2 NG Min Min Horizontal Venting Stand Offs Brackets 90 Elbow Termination Cap 9 229mm...

Страница 21: ...cal Venting Configurations IMPORTANT The vertical vent heat shield included with this fireplace must be installed for every type of venting application Refer to 11 5 Vent Heat Shield Assembly Installa...

Страница 22: ...the screw holes on the vertical vent heat shield 8 The 1 in 25 mm vent stand off tab will rest on top of the vent pipe providing the required minimum 1 in 25 mm clearance from the vent pipe surface Se...

Страница 23: ...0ft 6 1m Horizontal 20ft 6 1m Vertical Figure 11 10 Natural Gas Combination Venting MAXIMUM 20ft 6 1m Horizontal 20ft 6 1m Vertical Figure 11 11 LP Gas Combination Venting After the first elbow 3 ft 9...

Страница 24: ...Kit E 8 Flex Pipe Collar F 8 Pipe on Fireplace or Extension Kit G 800 WPT 3 Wall Pass Through Thimble Figure 11 12 Assembly and Installation of 800 1 Series 1 Mount the required wall pass through thim...

Страница 25: ...r veranda porch deck or balcony Must be fully opened on a minimum of two sides 12 in 305 mm 12 in 305 mm N Between two horizontal terminations 12 in 305 mm 12 in 305 mm O Between two vertical terminat...

Страница 26: ...12 7 5 2 27 Over 20 12 to 21 12 8 0 2 44 CAUTION This appliance must not be connected to or joined with any chimney flue serving any other appliance Approved Cap Approved vent pipe Roof pitch X 12 Dis...

Страница 27: ...cord 1 Fan housing cover plate 3 Wire nuts 1 Speed control mounting bracket 2 Fan wire connectors 1 Speed Control NOTE A junction box cover and hardware must be purchased to mount the speed control CA...

Страница 28: ...ontrol wires with provided wire nuts Run 110 VAC to fan speed control then from the fan speed control through the romex connector on the register bracket Secure grounding wire to the grounding screw i...

Страница 29: ...ng bracket to the junction box with the 2 screws provided 5 Center the register cover over the fan housing cover plate to install Secure register cover to stud wall with the provided mounting screws 6...

Страница 30: ...king out one of the 2 hinge screws until the access cover is able to pivot away from the glass frame 3 Loosen but do not remove 2 wing nuts securing component upper heat shield 4 Remove heat shield 5...

Страница 31: ...and push back to desired position 3 Lower the screen front until the notched tabs are firmly in position To remove lift up and out of slots Safety barriers are available in various colors See your lo...

Страница 32: ...OTE To avoid damage and prolong the life of halogen bulbs never touch with bare hands Always use a soft cloth when handling 13 3 Light Kit 13 3 1 Install Light Kit Figure 13 3 Screw Location on Burner...

Страница 33: ...r positioning burner venturi over burner orifice align ing burner tube with mounting cradles on control board Re install burner venturi housing 4 Reinstall burner cover aligning holes in cover to corr...

Страница 34: ...ey Transmission Thermostat OFF ON SMART Set Point Temperature Level State Flame ON Fan Lights CPI Mode Key Lock Room Temperature Low Battery Alarm Pilot Igniter Flame Sensor Red boot Black boot Black...

Страница 35: ...ton again The pilot will shut down indicating the remote has taken over The system is now initialized 4 Set the ON OFF rocker switch to ON position to operate fireplace with the remote control SW1 But...

Страница 36: ...screen The remote control can operate as a room thermostat The thermostat can be set to a desired temperature to control a room s comfort level To activate this function 1 Press the thermostat key The...

Страница 37: ...Press the mode key to index to light icon 2 Press the up or down arrow keys to adjust the intensity level 15 9 Accent Light Kit Figure 15 6 Accent Light Remote Operation Remote control battery lifesp...

Страница 38: ...r ignition the IFC control module will stop sparking for approximately 35 seconds After this wait time the IFC control module will start the second try for ignition by sparking for approximately 60 se...

Страница 39: ...ontrol ON OFF button After approximately 2 seconds press the remote control ON OFF button again The IFC control module will reset and the ignition sequence will start again Reset By Cycling Flame In t...

Страница 40: ...AND DOES NOT AFFECT THE PERFORMANCE OR LONGEVITY OF THE FIREPLACE This appliance is equipped with an ignition device which automatically lights the pilot DO NOT try to light the pilot by hand BEFORE O...

Страница 41: ...urn Gas Off to Appliance and call your service technician or the gas supplier NOTE When the fireplace is initially lit condensation will appear on the glass This is normal in all gas fireplaces and wi...

Страница 42: ...t with all other gas appliances on or at full capacity in the house for proper pressure reading 1 Loosen inlet IN pressure tap screw counter clockwise 2 Attach manometer using a 1 4 in 6 mm I D hose 3...

Страница 43: ...to venturi opening will create dramatic results Adjust at slight increments until desired look is achieved Always burn the fireplace for at least 15 minutes and allow the appliance time to cool befor...

Страница 44: ...o burn for 15 minutes If flames indicate there is excessive draft flickering short flames a restrictor may be necessary If flames indicate insufficient draft lifting or ghosting flames a previously in...

Страница 45: ...upplier No LP in tank Check LP propane tank Refill if necessary Wiring disconnection Use wiring schematic in this manual to determine that all wiring connections are secure and correct Pilot flame not...

Страница 46: ...ss Frame Assembly page 29 Improper vent cap installation Adjust if necessary Vent cap blockage Remove debris if necessary Improper pitch on horizontal venting 1 4 in 6 mm rise per foot is required on...

Страница 47: ...ted from electrical current and cleaned vacuumed every six months The bearings are sealed and require no oiling IMPORTANT ANY SAFETY SCREEN OR GUARD REMOVED FOR SERVICING MUST BE REPLACED PRIOR TO OPE...

Страница 48: ...47 LP Gas Orifice 47 700 596 Pilot Assembly Natural Gas NCK SL42 SP Natural Gas Conversion Kit 700 596 1 Pilot Assembly LP Gas LCK SL42 SP LP Gas Conversion Kit 700 408 Remote Control SL42 035 Burner...

Страница 49: ...cept on Hussong Manufacturing Co Inc s behalf any additional obligation of liability connected with the unit It is expressly agreed and understood that this warranty is Hussong Manufacturing Co Inc s...

Страница 50: ...lf any additional obligation of liability connected with the unit Hussong Manufacturing Co Inc may fully discharge all obligations with respect to this Lifetime Warranty by refunding the wholesale pri...

Отзывы: